Features
The RMS "Pelikan" constitutes a complex of independent units (intended for measurement of different parameters) that are interconnected into common information network. The RMS network is built using Ethernet IEEE 802.3 technology, it accommodates measurement devices and workstations as clients. The network includes two servers (main and hot standby), or alternatively, it can have no server at all. The RMS allows performing all commutations necessary for repair or calibration of measurement units in hot mode, without interrupting normal network operation.
Scheme of RMS "Pelikan"
Detector units and measurement devices
Measured value
|
DU, MD
|
Measurement range
|
Connection to the network
|
Dose rate of gamma radiation
| DBG-S11D | 0,1 μSv/h ÷ 10 mSv/h | to BOP-1M
|
UDMG-100
BDMG-200
|
10-7 ÷ 10 Sv/h
|
to BOP-1M
|
BDMG-101
|
5·10-5 ÷ 1000 Sv/h
10-5 ÷ 103 Gy/h
|
to BOP-1M
|
Dose rate of neutron radiation
|
UDMN-100
BDMN-200
|
10-7 ÷ 0,1 Sv/h
|
to BOP-1M
|
Volumetric activity of alpha and beta-emitting radionuclides
|
UDA-1AB
|
α: 0,01 ÷ 2·105 Bq/m3
β: 0,1 ÷ 107 Bq/m3
|
RS-485 and Ethernet
|
Volumetric activity of beta-emitting noble gases
|
UDG-1B
UDG-03D
|
104 ÷ 6·109 Bq/m3
(by Kr-85)
| RS-485 and Ethernet |
Volumetric activity of beta-emitting noble gases and gases with tritium and carbon-14
|
UDGB-01T;
UDGB-01T1
|
104 ÷ 5,0·109 Bq/m3
(by Kr-85)
|
RS-485 and Ethernet
|
UDGB-02T
|
109 ÷ 5,0·1015 Bq/m3
(by Kr-85)
|
Volumetric activity of radioiodine
|
UDI-1B
|
3,7·10-2 ÷ 3,7·106 Bq/m3
|
RS-485 and Ethernet
|
Volumetric activity in liquids
|
UDGP-01
|
1,5·103 ÷ 3·108 Bq/m3
(by Cs-137)
|
to BOP-1M
|
Parameters of air flow in the ventilation systems:
|
|
UPPVM
|
1,0 ÷ 20,0 m/s
|
RS-485 and Ethernet
|
|
0 ÷ +80 °Ñ
|
|
10 ÷ 95 %
|
Accessory
BOP-1M/BOP-1MD: Data processing and transmission unit |
- Processing of data incoming from detecting blocks UDMN-100, DBG-S11D, UDKG-100, BDMG-101, BDRG - 47R
- Data transmission to the network
- Data transmission to the mobile computer
- Storage of thresholds values and parameters of detecting blocks
- Power supply and diagnostics of detecting blocks
- Generation of the alarm signals of the excess of preset thresholds
- Data backup in the non-volatile memory
- Display of measured values on external display devices or on the integrated display (BOP-1MD)
|
Radiation monitoring rack (RM Rack) | The radiation monitoring stand (RMS) is designed for continuous monitoring of radiation parameters in premises and technological systems at nuclear facilities. RMS can be used as a structural element of the lower-level of automation radiation monitoring systems at nuclear power plants and other nuclear facilities that involved in obtaining, processing, use and storage of radioactive materials. |
BAS/BAS-1s: external alarm |
Generation of audible and visual signals of the excess of preset thresholds RMS monitors
|
Adjustment unit PN-PC | |
BI-2: External display & alarm unit |
- Display of data received from equipment of Automated Radiation Monitoring System (ARMS)
- Audible and visual alarms on exceeding preset thresholds of the ARMS equipment
- individual threshold setting for each measurement channel
- Audible alarm: 80-100 dB at a distance of 1 m
- Visual alarm: red, yellow, green
|
RMS Workstation operator console | Organization of interaction of the RMS Server and Monitors. |